Description
The HC-Air fan ventilation module is an essential service accessory to be used when transferring hydrocarbon refrigerant and should feature in the risk assessment process.
Good ventilation in the working area will ensure that any vapour from a leak or release will be rapidly dispersed. The fan module is placed at floor level near the working area and can be plugged in up to 5m away. It is recommended to switch the fan on before refrigerant handling commences.
Please contact us on sales@rda-eng.com for availability and pricing
More Information
Safety Procedure for the work area where HC systems are being serviced:
- The area must be well ventilated
- There must be no source of ignition within 3m of the system
- The area must be monitored with a hydrocarbon leak detector
Recommended Procedure for Servicing HC Refrigerant Equipment:
- Plug in the HC-Air Fan Ventilation Module 3m from the working area and position at floor level
- Plug in the RDA HC-3 3m from the working area and recover the hydrocarbon refrigerant
- When the low-pressure lamp has illuminated switch the unit to low pressure override and allow to run for 2 minutes
- Pressurise the system with OFN (Oxygen Free Nitrogen) to just above atmospheric pressure
- Using a HC Leak Detector check that no hydrocarbon refrigerant is in the air before lighting the brazing torch
- Un-braze the connections and complete the service operation
Training Engineers working with HC refrigerants should be trained in accordance with the specification EN378-4:2008 Annex E. Please contact Cool Concerns Ltd for training and consultancy – www.coolconcerns.co.uk